Product Characteristics #
NORVI-EX-ANI
ADS1115 16 bit ADC ADC
4 x 4 – 20mA Analog Inputs
Product Certifications #
Product is certified to comply with CE Standards
2014/30/EU- Electromagnetic Compatibility (EMC)
Annex III, Part B, Module C

EN 61131-2:2007
EN 61010-1:2010+A1:2019
EN IEC 61010-2-201:2018
Product Specifications #
Range of Product | NORVI EX |
Product type | I/O Expansion Module |
Rated supply voltage | 24V DC |
Discrete input number | 4 x 4 – 20mA Analog Input |
Communication | I2C |
Supply voltage limits | 9.4….28.8V |
Inrush current | <=10A |
Maximum Input Voltage | 36V DC |
Measurement Range | 0 – 20mA / 4 – 20mA |
Discrete input current | 20 mA Max. for input |
Input impedance | 10R Ohm for input |
Local signaling | 1 LED green for PWR |
Electrical connection | Fixed screw terminal block for inputs and outputs (pitch 5.08 mm) |
Mounting support | Top hat type TH35-15 rail conforming to IEC 60715 Top hat type TH35-7.5 rail conforming to IEC 60715 Plate or panel with fixing kit |
Height | 90.50 mm |
Depth | 56.60 mm |
Width | 60.60 mm |
Product weight | 0.18 Kg |
ADC Chip | ADS1115 |
I2C Address | Fixed Address Type 0x48 Address configurable – 0x48 0x49 – 0x4A – 0x4B |
Interrupt Pin | Not Connected |
Environment #
Resistance to electrostatic discharge | 4kV on contact 8kV on air |
Resistance to electro magnetic fields | 10 V/m (80 MHz …… 1GHz) 3 V/m (1.4 MHz …… 2 GHz) 1 V/m (2 MHz …… 3 GHz) |
Immunity to microbreaks | 10 ms |
Relative humidity | 10….95% without condensation in operation |
IP degree of protection | IP20 |
Operating altitude | 0…2000m |
Operating Temperature | –40°C to +125°C |
Storage altitude | 0…3000m |
Shock resistance | 15 gn for 11 ms |
Dimensions #

Terminal Layout #

GPIO Allocation #
ADS1115 ADC | I/O |
---|---|
A3 | A0 – ANALOG INPUT 0 |
A1 | A1 – ANALOG INPUT 1 |
A2 | A2 – ANALOG INPUT 2 |
A0 | A3 – ANALOG INPUT 3 |
I2C SDA | GPIO16 |
I2C SCL | GPIO17 |
Expansion Port #
The expansion port of the NORVI IIOT Controllers can be utilized for external sensor connections where raw GPIO connections are required or they can be used to plug NORVI Expansion Modules
Browse NORVI Expansion Product range
How to Connect NORVI Expansion Modules


I2C Address Setting #
In the basic units of NORVI Analog Input Expansion, the Address of the unit is fixed to 0x48 at the factory.
On modules with Address configuration options, I2C Address of the expansion module can be configured by switching DIP Switches in the bottom of the expansion module. The device can be configured in 4, I2C addresses using the 4, switches.